通风条件下CO_2浓度的测量与预测模型的建立 被引量:2

Measurement and prediction model of CO_2 concentration in ventilation conditions
下载PDF
导出
摘要 以CO2为示踪气体,采用干冰和人体呼吸产生CO2两种方法,在不同换气次数条件下测定了CO2浓度变化规律,建立了室内CO2浓度预测模型。由此得到存在门窗缝隙渗风时,室内人员处在正常工作状态下的室内外CO2浓度差与换气次数的函数关系,从而可算出最小换气次数。由实验可知,自然渗风时无人房间CO2浓度呈指数衰减;满足室内空气质量要求与节能要求的最小新风量为35m3/(人.h)。 Taking CO2 generated from dry ice and human breath as the tracer gas,measures changing patterns of the CO2 concentration for different air changes and establishes the prediction model of indoor CO2 concentration.Wherefrom obtains the relationship of the CO2 concentration difference between indoor and outdoor and air changes when occupants are in a normal working state and there exists air infiltration through the gaps of doors and windows,by which the minimal air changes can be obtained.The experimental results show that when considering the air infiltration,the concentration decays exponentially in a non-occupied room,and the minimal fresh air volume is 35 m3 per person per hour for meeting the requirements of indoor air quality and energy saving.
出处 《暖通空调》 北大核心 2010年第3期103-106,共4页 Heating Ventilating & Air Conditioning
关键词 换气次数 CO2浓度 通风 预测模型 air changes CO2 concentration ventilation prediction model
  • 相关文献

参考文献10

  • 1秦喜庆,麻志杰,张庆军.居室CO_2浓度变化规律数学模型的建立及应用[J].佳木斯大学学报(自然科学版),2002,20(2):218-220. 被引量:1
  • 2陈艳平 安世奇 孙明.变风量系统中室内CO2浓度的模糊积分控制.冶金自动化,2005,:879-882. 被引量:1
  • 3Di Giaeomo S M. Differential CO2 based demand control ventilation [J]. Energy Engineering, 1999,96 (5): 58-76. 被引量:1
  • 4Schell M. Saving energy and optimizing air quality using carbon dioxide[J]. Energy Engineering, 1998, 95(2): 19-33. 被引量:1
  • 5ASTM E 741-2000 Standard test method for determining air change in a single zone by means of a tracer gas dilution [S]. America: ASTM International, 2000. 被引量:1
  • 6Yu C K, Chow T T. CO2 concentration in a typical Hong Kong classroom [C] //Proceedings of the 4th International Conference on Indoor Air Quality, Ventilation & Energy Conservation in Buildings. Hong Kong: City University of Hong Kong, 2001:329-338. 被引量:1
  • 7李晶,王跃思,刘强,王明星.北京市两种主要温室气体浓度的日变化[J].气候与环境研究,2006,11(1):49-56. 被引量:24
  • 8戴自祝,邵强.建筑物需要的新风量[J].中国卫生工程学,2001(2):8-13. 被引量:3
  • 9崔家昌,陈丽华,洪声,等.GB/T18204.18-2000公共场所室内新风量测定方法[S].北京:中国标准出版社,2000. 被引量:1
  • 10ASHRAE. ASHRAE Standard 62-1999 Ventilation for acceptable indoor air quality [S]. Atlanta, 1999. 被引量:1

二级参考文献33

  • 1杨昕,王明星.陆面碳循环研究中若干问题的评述[J].地球科学进展,2001,16(3):427-435. 被引量:63
  • 2HoughtonJ著 戴晓苏 石广玉 董敏 等译.全球变暖[M].北京:气象出版社,1998.. 被引量:12
  • 3IPCC.Climate Change 1995:Impacts,Adaptations and Mitigation of Climate Change:Scientific-Technical Analyses.Cambridge:Cambridge University Press,1995.745~772 被引量:1
  • 4Gunter W D,Wong S,Cheel D B,et al.Large CO2 sinks:their role in the mitigation of greenhouse gases form an international,national (Canadian) and provincial (Alberta)perspective.Applied Energy,1998,61:209~227 被引量:1
  • 5Raich J W,Potter C S.Global patterns of carbon dioxide emissions from soil.Global Biogeochemistry Cycle,1995,9:23~26 被引量:1
  • 6Crutzen P J.Methane's sinks and sources.Nature,1991,350:380~381 被引量:1
  • 7Crutzen P J.On the role of CH4 in atmospheric chemistry:sources,sinks and possible reductions in anthropogenic sources.Ambio,1995,24:52~55 被引量:1
  • 8Keeling C D,Bacastow R B,Bainbridge A E ,et al.At mospheric carbon dioxide variations at Mauna Loa Observatory,Hawaii.Tellus,1976,28:538~551 被引量:1
  • 9Seiler W,Conrad R,Scharffe D.Field studies of methane emission from termite nests into the atmosphere and measurement of methane uptake by tropical soils.J.Atmos.Chem.,1984,1:171~186 被引量:1
  • 10Khalil M A K,Rasmussen R A,Moraes F.Atmospheric methane at Cape Meares:analysis of a high resolution data base and its environmental implications.J.Geophys.Res.,1993,98:14753~14770 被引量:1

共引文献25

同被引文献22

  • 1贾代勇,耿世彬,袁印奎,杨家宝,韩旭.基于CO_2和TVOC浓度的空调新风随机控制系统[J].暖通空调,2004,34(6):14-16. 被引量:14
  • 2蔡启明,吴海燕.成年男子心率与能量代谢率关系试验研究[J].人类工效学,1996,2(2):42-45. 被引量:8
  • 3邓大跃,蔡金岩,周酉酉,陈双基.教室内二氧化碳污染和新风量测定[J].环境科学与技术,2007,30(9):45-47. 被引量:18
  • 4Clements-Croome D J, Awbi H Ventilation rates in schools [ J ]. 2008, 43 (3) : 362-367. 被引量:1
  • 5B, Bako-Biro Z, et al. Building and Environment Ginestet S, Marchio D. Control tuning of a simplified VAV system: Methodology and impact on energy consumption and IAQ [J]. Energy and Buildings, 2010, 42(8) : 1205-1214. 被引量:1
  • 6Yu B F, Hu Z B, Liu M, et al. Review of research on air- conditioning systems and indoor air quality control for human health [ J ]. International Journal of Refrigeration, 2009, 32 ( 1 ) : 3-2O. 被引量:1
  • 7Sepp anen O A, Fisk W J, Menden M J. Association of Ventilation Rates and COz Concentrations with Health and Other Responses in Commercial and Institutional Buildings[ J]. Indoor Air, 1999, 9(4) : 226-252. 被引量:1
  • 8Costanzo S, Cusumano A, Giaconia C. Ventilation Rates and Unsatisfied Percentage from Indoor CO2 Concentration [ J ]. Indoor and Built Environment, 2011, 20(2), 232-245. 被引量:1
  • 9MacHattie L A. Graphic visualization of the relations of metabolic fuels: heat: 02: CO2: H20: urine N[J]. Journal of Applied Physiology, 1960, 15(4) : 677-683. 被引量:1
  • 10Salam M A, Noguchi T. Impact of human activities on carbon dioxide ( COz ) emissions: a statistical analysis [J]. Environmentalist, 2005, 25 ( 1 ) : 19-30. 被引量:1

引证文献2

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部