期刊文献+

输电铁塔冷弯角钢构件轴心受压承载力分析及试验研究 被引量:6

Analysis and Experimental Study on Ultimate Bearing Capacity of Structural Members of Cold-Bending Angle Steel for Transmission Tower Under Axial Compression
下载PDF
导出
摘要 输电线路铁塔应用冷弯型钢,可以提高输电铁塔设计水平,降低钢材用量。文章结合输电铁塔的结构特点,选取不同截面、长细比的冷弯角钢构件进行轴心受压承载力试验和有限元分析,得到了输电铁塔用冷弯角钢轴心受压构件的荷载-应变发展规律和极限承载力,并与现行设计规范承载力计算值进行了对比。分析结果表明,现行规范体系不适合我国输电铁塔冷弯型钢轴心受压构件的强度设计。通过对试验和理论分析结果进行拟合,确定了输电铁塔冷弯型钢轴心受压构件稳定系数曲线,提出了输电铁塔冷弯型钢构件承载力计算的修正意见。 The design level of transmission towers in China can be improved and steel product consumption for it can be reduced by adopting cold-bending profile steel to transmission tower. Based on the structural features of transmission tower, the cold-bending angle steel members with different cross-sections and slenderness ratios are chosen for bearing strength test under axial compression and finite element analysis, thus the load-strain law and ultimate bearing capacities of cold-bending angle steel members of transmission towers under axial compression are obtained, and the obtained ultimate bearing capacities are compared with the bearing capacities calculated by active design specifications. Analysis results show that current specification system is unsuit to the strength design of axial-compressed cold-bending angle steel members for transmission towers in China. Through the fitting of test results with theoretical analysis results, the stability coefficient curve of axial-compressed cold-bending angle steel members for transmission towers is decided and some modification suggestions on bearing capacity calculation of cold-bending angle steel members for transmission towers are proposed.
出处 《电网技术》 EI CSCD 北大核心 2010年第2期194-199,共6页 Power System Technology
基金 国家电网公司科技项目(SGKJ2007[117])
关键词 输电铁塔 冷弯角钢 构件试验 稳定系数 transmission tower cold-bending angle steel member test stability coefficient
  • 相关文献

参考文献15

二级参考文献66

共引文献323

同被引文献71

引证文献6

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部