摘要
介绍了蒙西电网运行中的合成绝缘子机械负荷和电气抽检试验,发现合成绝缘子运行3年后,其金具与棒芯之间的机械负荷明显下降,而且尽管电气试验未表明绝缘性能下降,但也存在着一些不可忽视的问题。
The results of mechanical and electric test on the silicon rubber insulator were stood and analyzed in the paper. It has been found that the mechanical load of the silicon rubber insulator is dcreased in connection zone between core and end fitting three years later, and that the electrical strength is not changed apparently.
出处
《高电压技术》
EI
CAS
CSCD
北大核心
1998年第3期87-87,93,共2页
High Voltage Engineering
关键词
合成绝缘子
机电试验
绝缘子
电力网
silicon rubber insulator mechanical and electric tests analysis