摘要
通过分析蒙城地震台2008年6月3日的雷击灾害的成因,发现台站原先的防雷系统存在不合理之处,并对防雷系统进一步改造,通过雷雨期的检验,收到了良好的效果。同时,警示其他台站有必要评估本台站的防雷效果,系统是否存在隐患之处,以免遭受类似蒙城地震台的惨痛损失。
By the case study of disaster struck of lightning at Mengcheng Seismic Station on June 3, 2008, it is found that the design of original lightning protection system is unreasonable. Passing a thunderstorm season, it was verified that the reconstructed lightning protection system is effective. Meanwhile, the case warns other seismic station that it is necessary to estimate the effective of lightning protection system in the station in order to find any hidden trouble and prevente from the severe lost as the Mengcheng Seismic Station.
出处
《地震地磁观测与研究》
2009年第6期91-99,共9页
Seismological and Geomagnetic Observation and Research
关键词
雷电灾害
防雷系统
防雷维护
lightning disaster, lightning protection systems, mine maintenance