摘要 深埋地下工程的地层温度比较低,导致其室内的平均辐射温度偏低,传统空调参数不能满足工作人员的需要。本文以Fanger热舒适方程及PMV-PPD评价指标为理论依据,采用Airpak软件对夏季南京某深埋地下工程房间的室内热环境情况进行了模拟。结果表明,平均辐射温度低于室内空气温度,室内相对湿度为60%时,最佳空气设计温度为25.7℃。 Stratum temperature of deep underground engineering is low, thus its indoor mean radiate temperature is low too. And the traditional air conditioning parameters can't reach the thermal eomfort's requirement. Then a deep underground air-conditioning room's thermal environment in Nanjing in summer was simulated by Airpak based on the Fanger thermal comfort equation and PMV-PPD. The results showed that the mean radiate temperature is lower than the indoor air temperature and the best design temperature was 25.7℃ when the RH was 60%.
机构地区 解放军理工大学
出处 《制冷空调与电力机械》 2009年第4期53-56,52,共5页 Refrigeration Air Conditioning & Electric Power Machinery
关键词 地下工程 CFD 热舒适 空调设计温度 模拟 underground engineering CFD thermal comfort air-conditioning designed temperature simulation
  • 相关文献

参考文献4

  • 1ASHRAE Handbook-Fundatmentals(SI)[M]. Atlanta: ASHRAE, 2005. 被引量:1
  • 2ISO. International Standard 7730. Moderate thermal environment -determination of the PMV and PPD indices and specification of the conditions for hermal comfort [S]. Geneva: International Standard Organization, 1984. 被引量:1
  • 3金招芬,朱颖心主编..建筑环境学[M].北京:中国建筑工业出版社,2001:161.
  • 4艾青云.地下工程空气调节基础[Z].南京:工程兵工程学院,1997 被引量:2

共引文献1