直流偏磁引起的500kV电力变压器振动和噪声的现场测量与分析 被引量:61

Field Monitoring and Analysis on Vibration and Noise of 500 kV Electrical Transformer under DC Current Biasing
下载PDF
导出
摘要 设计了500 kV单相电力变压器振动与噪声在线同步监测方案,并通过振动与噪声传感器及相应的数据采集和分析系统实现了对广东惠州500 kV变电站单相电力变压器直流偏磁条件下的振动与噪声的实时监测。监测得到了500 kV电力变压器外壳上典型位置在直流偏磁前后的振动与噪声的时域波形数据,分析得到了500 kV单相变压器振动与噪声信号在直流偏磁前后的频率范围。试验结果表明:直流偏磁条件下电力变压器的振动与噪声幅值增加明显且频谱中出现了大量高次谐波,对于变压器的运行有着不利的影响。 In order to observe the influence caused by the DC biasing current through the neutral point of the power transformer, a new on-line vibration and sound monitoring program was designed with use of both qualified vibration and sound sensors at the same time. The experiment was operated in Huizhou 500 kV substation and a 500 kV single phase electrical transformer was chosen as experimental object. Based on the experiment platform, steady and clear vibration and sound waveform before and after the DC biasing condition was recorded and spectrum analysis was also achieved based on the data monitored. In conclusion, DC biasing is harmful for power transformers and the result of this research provides valuable reference to the on-line vibration and sound monitoring system of transformers.
出处 《高压电器》 CAS CSCD 北大核心 2009年第3期93-96,共4页 High Voltage Apparatus
关键词 变压器振动 噪声 直流偏磁 在线监测 频谱 transformer vibration noise DC biasing on line monitoring spectrum
  • 相关文献

参考文献7

二级参考文献16

  • 1彭文达 庄稼人 等.断路器的燃弧区间与三相分闸不同期性[J].高压电器,1981,(6):10-13. 被引量:3
  • 2.DL437—91.高压直流接地技术导则[S].,1991.. 被引量:1
  • 3.接地极工程选址报告[R].武汉:中南电力设计院,1997.. 被引量:1
  • 4.三峡直流咨询报告[R].上海:华东电力设计院,1997.. 被引量:1
  • 5.DL/T572--1995.电力变压器运行规程[S].,.. 被引量:1
  • 6钟连宏.三峡至常州±500 kV直流输电工程咨询《直流对地下金属结构及接地变压器影响》[A]..武汉:国家电力公司武汉高压研究所技术报告[C].,1997.. 被引量:1
  • 7[1]The McGraw-Hill Companies.Monitoring Clamping Pressure with Vibro-acoustics[M].Electrical World,November/December 1999,New York. 被引量:1
  • 8[2]E.Reiplinger.Study of Noise Emitted by Power Transformers Based on Today Viewpoint[R].CIGRE Paper,1988,No. 12-08. 被引量:1
  • 9[3]V.Sokolov etc.Effective Methods of Assessment of Insulation System Conditions in Power Transformers:A View Based on Practical Experience[R].CIGRE Paper ,1999:659-667. 被引量:1
  • 10[4]M.N.Bassim,Mike Dudar etc. Application of Acoustic Emission for Nondestructive Evaluation[J].IEEE Trans. on Power Delivery,1993, Vo1.8, No.1:281-284. 被引量:1

共引文献262

同被引文献623

引证文献61

二级引证文献551

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部