期刊文献+

多端辐射状输电线路故障测距的一种实用算法 被引量:8

A PRACTICAL FAULT LOCATION ALGORITHM FOR MULTI-TERMINAL TRANSMISSION LINES WITH RADIAL STRUCTURE
下载PDF
导出
摘要 传统的利用单端电压电流工频分量的输电线路故障测距算法,较难解决多端输电线路故障定位问题。文中基于模量分析提出一种多端输电线路故障测距的实用算法,特.或为:端与瑞之间,数据不要求同步,不需实时通信;测距方程不需送代求解;不需故障前负荷状态信息,不需区分短路类型;原理上,与过渡阻抗大小和性质、电源等值阻抗变化、系统外部元件变化、线路本身耦合等诸多因素无关;线路建模采用RLC全分布参数线路模型。大量暂态仿真计算表明,该方法有效。 Generally. algorithms using one-terminal voltage and current data can not be used for locating the faults on multi-terminal lines. On the basis of modal analysis theory. this paper describes a new accurate fault location algorithm for mu1ti-terminal lines. The developed algorithm has the following features' The measurements taken at all ends are not required to besynchronized: The equations of fault location are solved noniterativeIy: The pre-fault conditions and the fault types are notrequired to be prepared: Theoretically, the technique is independent of the transient impedance, the source impedance, andthe coupling of the line itself: Both series impedance and shunt admittance effects are modeled. A large number of transientsimulation tests show that the algorithm described in the paper is feasible.
出处 《电力系统自动化》 EI CSCD 北大核心 1998年第2期21-25,45,共6页 Automation of Electric Power Systems
关键词 多端输电系统 故障测距 故障分析 输电线路 multi-terminal transmission system fault location fault analysis
  • 相关文献

同被引文献63

引证文献8

二级引证文献115

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部