摘要
介绍单元式空气调节机标准中水冷式空调机的制冷综合部分负荷性能系数IPLV(C)的测试计算方法,对空调机无法准确卸载到75%,50%以及25%负荷能力的情况的插值计算方法进行分析,提出3种插值方案,并通过试验对比这3种插值方案计算IPLV(C)结果的差异。
Introduces testing (cooling) for water cooled unitary and calculation methods of integrated part load value air conditioner. Analyzes interpolation method for situation that air conditioner can not unload to 75%, 50% and 25% capacity, and points out three linear interpolation methods, compares the IPLV(C) results using three linear interpolation methods by test.
出处
《制冷与空调》
2008年第4期32-35,56,共5页
Refrigeration and Air-Conditioning