摘要 提出了一种基于集中参数线路模型的高压/超高压T接线路测距新算法。该算法在考虑线路分布电容的前提下,仅采用故障电压序分量进行故障测距,具有不受故障后电流互感器饱和影响的优点。对于对称类故障,用电压正序故障分量进行测距;对于非对称类故障,用电压负序故障分量进行测距。对该算法分别就单回线-单回线T接线路、单回线-双回线T接线路、双回线-双回线T接线路接线方式下测距做了详细讨论,并提出了新的故障分支判据,依次计算每个分支的故障距离,比较后即可准确判断故障分支。ATP仿真验证表明,对于三端同步及不同步采样电压量数据,测距精度都在1%以内。 A fault locating algorithm based on the transmission line model with lumped parameters is presented for HV / EHV T- type connection transmission lines,which considers the distributed capacitance of lines and uses the sequence components of fault voltage in fault locating to avoid the influence of saturated CT after fault. Positive sequence component of fault voltage is used for symmetric faults and negative sequence component for non-symmetric faults. Different conditions are discussed in detail:single-line to single-line T-type connection,single-line to parallel-line T-type connection and parallel- line to parallel- line T- type connection. A new faulty branch criterion is proposed. The fault distance of each branch is calculated and compared to accurately determine which the faulty one is. ATP simulation indicates that the locating precision is within 1% with the synchronously or asynchronously sampled voltages at three terminals.
出处 《电力自动化设备》 EI CSCD 北大核心 2008年第9期31-35,共5页 Electric Power Automation Equipment
关键词 T接 超高压线路 多端测距 电压故障分量 T-type connection EHV line multi-terminal fault locating sequence components of fault voltage
  • 相关文献

参考文献15

  • 1全玉生,王晓蓉,杨敏中,严璋,李晓兵,于峥,康林贤,司鲁东,佟科,刘晓峰.工频双端故障测距算法的鲁棒性问题和新算法研究[J].电力系统自动化,2000,24(10):28-32. 被引量:46
  • 2NOVOSEL D,HART D G,UDREN E. Unsynchronized two terminal fault location estimation[J ]. IEEE Trans on Power Delivery, 1996, 11(4) : 130- 138. 被引量:1
  • 3JOHNS A T,JAMALI S. Accurate fault location technique for power transmission line[J ]. Proc Inst Elect Eng Gen Transm Distrib, 1990,137(6) :395-402. 被引量:1
  • 4PEREIRA C E M,Jr ZANETTA L C. Optimization algorithm for fault location in transmission lines considering current trans- formers saturation[J ]. IEEE Trans on Power Delivery,2005,20 (2) :603-608. 被引量:1
  • 5ZAMORA I,MINZMBRES J F,MAZON A J,et al. Fault location on two-terminal transmission lines based on voltages[J].IEE Proceedings - Generation,Transmission & Distribution,1996,143 (1):1-6. 被引量:1
  • 6BRAHMA S M,GIRGIS A A. Fault location on a transmission line using synchronized voltage measurements[JJ. IEEE Transactions on Power Delivery,2004,19(4) : 1619- 1622. 被引量:1
  • 7贺家李 ... ..电力系统继电保护原理[M],2004.
  • 8MINZMBRES J F,ZAMORA I,MAZON A J,et al. A new technique based on voltage for location on three- terminal transmission lines [J ]. Electric Power System Research, 1996,11 (1):130-138. 被引量:1
  • 9李胜芳,范春菊,郁惟镛.T型支接线路的自适应故障测距算法[J].电工技术学报,2004,19(10):59-64. 被引量:41
  • 10GIRGIS A A,HART D G,PETERSON W L. A new fault location technique for two and three-terminal lines[J]. IEEE Trans on Power Delivery, 1992,7(1 ) :98- 107. 被引量:1