期刊文献+

计及不同保护配置方案的继电保护系统可靠性 被引量:40

Reliability of Protection Relay Systems with Different Configurations
下载PDF
导出
摘要 微机保护装置的硬件可靠性已得到了很大提高,不同保护原理及配置方式已成为影响可靠性的主要因素。目前尚缺乏相应的可靠性模型,为此提出了一种新的计及不同保护配置模式的保护系统可靠性评估模型。基于马尔可夫方法,考虑2种故障模式即误动和拒动状态,推导出可以评估不同保护配置方案的可靠性模型,可计算保护系统误动和拒动的概率,为完善电网风险分析及可靠性评估方法提供了可用数学方法。算例证明了所提出方法的正确性。 Since the hardware reliability of microcomputer protection relays has been greatly enhanced, the main factors that influence the protection system reliability are protection principles and configurations. To assess the reliabilities of different protection principles and configurations, a novel reliability model is proposed. Based on the Markov method and considering two failure modes (false-function and fail-function), the new reliability model is derived. The method can be used to calculate the probability of false-function and fail-function. The method also provides a mathematical way to improve the system risk assessment and reliability analysis. The results of case study prove the correctness of the model.
出处 《电力系统自动化》 EI CSCD 北大核心 2008年第14期21-24,共4页 Automation of Electric Power Systems
基金 国家重点基础研究发展计划(973计划)资助项目(2004CB217908) 国家自然科学基金资助项目(50777068)~~
关键词 继电保护 可靠性 马尔可夫模型 电力系统 relay protection reliability Markov model power system
  • 相关文献

参考文献15

二级参考文献63

共引文献231

同被引文献333

引证文献40

二级引证文献312

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部