期刊文献+

基于改进故障点法的电压凹陷评估 被引量:14

Assessment of voltage sag based on improved fault positions method
下载PDF
导出
摘要 针对传统故障点法选取故障点带有盲目性的问题,提出了基于解析式的改进故障点法。算法考虑了电网传输线上的故障分布和故障类型,并根据电压凹陷深度和故障距离的关系曲线对传输线分区,将每个区间作为一个故障点,因此在每条传输线上只要设置较少数量的故障点,通过每个故障点的故障概率分布评估不同电压凹陷深度区间的凹陷频次。并由电压凹陷深度和故障距离的曲线确定不同电压限值的临界点,进而确定电网的凹陷域。提出的改进故障点法用于评估IEEE 30节点标准测试系统的电压凹陷频次,验证了该方法的正确性和实用性。所提方法适用于任何规模电网发生对称故障和不对称故障时的电压凹陷频次评估。 An improved fault positions method based on analytical expression is proposed for fault position selection to overcome the blindness of traditional methods. Considering the fault distribution and fault types of transmission lines,it divides the transmission lines according to the relationship curve between the voltage sag depth and fault distance and takes each division as a fault position. Thus fewer fault positions are set and their frequency of voltage sag is assessed by fault probability distribution. It calculates the critical points of different voltage threshold by the relationship curve to determine the vulnerable area. The application to IEEE 30-bus test system validates its correctness and practicality. It works for both symmetric and asymmetric faults of power grid of any size.
出处 《电力自动化设备》 EI CSCD 北大核心 2008年第6期66-69,73,共5页 Electric Power Automation Equipment
关键词 电压凹陷评估 解析式 改进故障点法 凹陷域 voltage sag assessment analytical expression improved fault positions method vulnerable area
  • 相关文献

参考文献16

二级参考文献42

  • 1[1]Dixon J,Tepper S,Moran L.Practical evaluation of different modulation techniques for current-controlled voltage source inverters [J].IEE Proceedings Electric Power Applications,1996,143(4): 301-306. 被引量:1
  • 2[2]Buso S,Malesani L,Mattavelli P.Comparison of current control techniques for active filter applications[J].IEEE Transactions on Industrial Electronics,1998,45(5): 722-729. 被引量:1
  • 3[3]Malesani L,Mattavelli P,Tomasin P.High performance hysteresis modulation technique for active filters [J].IEEE Transactions on Power Electronics,1997,12(5): 876-884. 被引量:1
  • 4[4]Elmitwally A,Abdelkader S,Elkateb M.Universal power quality manager with a new control schemes[J].IEE Proc.-Gener.Transm.Distrib.,2000,147(3):183-189. 被引量:1
  • 5[5]Saetieo S,Devaraj R,Torrey D A.The design and implementation of a three-phase active power filter based on sliding mode control[J].IEEE Transactions on Industry Applications,1995,31(5):993-999. 被引量:1
  • 6[6]Sedighy M,Dewan S B,Dawson F P.A robust digital current control method for active power filters [J].IEEE Transactions on Industry Applications,2000,36(4):1158-1164. 被引量:1
  • 7[7]Moran L A,Dixon J W,Wallace R R.A three-phase active power filter operating with fixed switching frequency for reactive power and current harmonic compensation[J].IEEE Transactions on Industrial Electronics,1995,42(4):402-408. 被引量:1
  • 8WAGNER V E. Power quality and factory automation[J]. IEEE Transactions on Industry Applications, 1990, 26(4): 39-42. 被引量:1
  • 9Sarmiento H G, Estrada E. A voltage sag study in an industry with adjustable speed drives[J]. IEEE Industry Applications Magazine,1996, 2(1): 16-19. 被引量:1
  • 10Bollen M H J, Qader M R, Allan R N. Stochastical and statistical assessment of voltage dips[C]. IEE Colloquium on Tools and Techniques for Dealing with Uncertainty, London, UK, 1998. 被引量:1