风冷热泵机组部分负荷变工况下优化风量的初步研究 被引量:3

Preliminary Study on Air Volume Optimization under Part Load and Variable Operating Condition for Air-cooled Heat Pump
下载PDF
导出
摘要 建立了风冷热泵机组冷凝器的数学模型,分析了风量调节方式对COP的影响,得到不同工况不同负荷率下的最优风量变化曲线。结果表明,同负荷率下工况的变化对最优风量比例影响较小,而负荷率的变化对最优风量比例影响较大。针对某特定机组,部分负荷率大于50%时应采用定风量调节,部分负荷率小于50%时应采用变风量调节;部分负荷率为25%时,选用最优风量COP可提高8%。同时,基于模拟结果,对风机选型也提出了新的看法。 The mathematical model of condenser of air-cooled heat pump was built. The influence of adjustment method of air volume to COP was analyzed. The changing curve of optimal air volume under different part load rate and operating conditions was gained. Results showed that the influence of operating condition to optimal air volume was slight ; the influence of part load rate to optimal air volume was great. Aimed at one special heat pump, variable air volume adjustment should be used when the part load rate was lower than 50%. Especially, when part load rate was 25% , the COP could increase by 8%. And based on the results, a new idea about selecting fan was presented.
作者 金星 张小松
机构地区 东南大学
出处 《流体机械》 CSCD 北大核心 2008年第4期63-67,共5页 Fluid Machinery
关键词 风冷热泵机组 变工况 部分负荷 风量调节 模拟 air-cooled heat pump variable operating condition part load~ air volume adjustment simulation
  • 引文网络
  • 相关文献

参考文献8

  • 1Yu F W, Chan K T. Advanced control of condensing temperature for enhancing the operating efficiency of aircooled chillers [ J ]. Building and Environment, 2005, 40:727-737. 被引量:1
  • 2Yu F W, Chan K T. Advanced control of heat rejection airflow for improving the coefficient of performance of air-cooled chillers [ J ]. Applied Thermal Engineering, 2006, 26:97-110. 被引量:1
  • 3张小松,夏燚,K.T.Chan.风冷冷水机组部分负荷时的节能优化运行策略与性能分析[J].暖通空调,2004,34(2):78-82. 被引量:23
  • 4Shi-ming Deng, Jhon Burnett. Performance monitoring and measurement for central air conditioning chiller plants in buildings in Hong Kong [ J ]. HKIE trans, 1997, 4(1) :7-12. 被引量:1
  • 5Yeung Tat Man. Performance evaluation of hotel chiller plant[ D]. Research Project:3.03, Department of Building Services Engineering, The Hong Kong Poly- technic University, 2000. 被引量:1
  • 6李苏泷,徐莉,朱海峰.水冷式冷水机组冷凝温度控制法研究[J].制冷学报,2005,26(4):59-62. 被引量:11
  • 7丁国良,张春路著..制冷空调装置仿真与优化[M].北京:科学出版社,2001:170.
  • 8吴业正.小型制冷装置设计指导[M].北京:机械工业出版社,1997.. 被引量:13

二级参考文献27

  • 1葛云亭,彦启森.冷凝器动态参数数学模型的建立与理论计算[J].制冷学报,1995,17(3):17-26. 被引量:26
  • 2Gordon J M, Ng K C, Chua H T et al. How varying condenser coolant flow rate affects chiller performance: thermodynamic modeling and experimental confirmation. Applied Thermal Engineering, 2000,(20):1149-1159. 被引量:1
  • 3Hawlader M N,Liu B M. Numerical study of the thermal-hydraunic performance of evaporative natural draft cooling tower. Applied Thermal Engineering, 2002,(22): 41-59. 被引量:1
  • 4Trane CenTraVac Centrifugal Chiller. Version 24.06, REVL 10001. 被引量:1
  • 5ARI 550/590-1998. 被引量:1
  • 6Deng Shi-ming, Burnett John. Performance monitoring and measurement for central air conditioning chiller plants in buildings in Hong Kong. In: HKIE Trans.1997,4(1).7-12 被引量:1
  • 7Yeung Tat Man. Performance evaluation of hotel chiller plant, Research Project:3.03, Department of Building Services Engineering. The Hong Kong Polytechnic University, 2000 被引量:1
  • 8Austin Stephen B. Optimum chiller loading. ASHRAE J, 1991,33(7):40-43 被引量:1
  • 9ChanKT.Operating efficiency of air-cooled chillers at below-design ambient temperatures[A]..2000港宁空调技术及设计研讨会论文集[C].,2000.. 被引量:1
  • 10Mike Smith, Greg King. Energy-saving controls for air-cooled water chillers. Building Services J, 1998:47-48 被引量:1

共引文献43

同被引文献28

引证文献3

二级引证文献2

;
使用帮助 返回顶部