一起一次接线原因导致的主变差动保护动作分析

An analysis of malfunction on the differential protection of main transformer caused by inappropriate main electric connection
下载PDF
导出
摘要 在中性点非直接接地系统中发生单相接地时,因接地电流很小,一般不会导致电流保护动作。但在某变电站中因一次接线原因在发生单相接地时,导致了主变差动保护动作,在分析动作原因的基础上,对此种接线方式可能引起的危害进行了初步分析,提出了解决方法。 When single-phase-to-earth fault occurs in non-direct-grounding neutral system, the current relay generally will not operate since the amplitude of grounding current is too small. But when such fault occurred in a station discussed in this paper, the differential protection of main transformer operated because of its inappropriate main electric connection. Based on the malfunction analysis, the harm brought by such main electric connection is discussed primarily and a solution is proposed.
出处 《继电器》 CSCD 北大核心 2008年第1期87-89,共3页 Relay
关键词 中性点不接地系统 单相接地 差动保护 non-direct-grounding neutral system single-phase-to-earth fault differential protection
  • 相关文献

参考文献3

  • 1平绍勋主编..电力系统内部过电压保护及实例分析[M].北京:中国电力出版社,2006:328.
  • 2GB50227-95.并联电容器装置设计规范[S].[S].,.. 被引量:17
  • 3GB3983.2-89.高电压并联电容器[S].[S].,.. 被引量:2