摘要
论述了500 kV无人值班变电站监控系统与集中监控系统间保护信息传输实现独立通道的必要性和可行性,借助对IEC 60870-5-103保护信息传输规约的特定报文扩充,在集控系统实现面向保护对象的自动建模,实现保护定值区切换、软压板投退、保护告警复归等远方操作功能,总结了集控系统接入保护信息的生成和试验的主要步骤,并在华东电网两座500 kV变电站无人值班变电站站控系统和两套集控系统中成功试运行。
The necessity and feasibility of realizing independent channels for protection information transmission between the monitoring system and the centralized monitoring system of the 500 kV unattended substation are discussed. Through special packet expending of IEC 60870-5-103 protection information transmission protocol, the protection object oriented automatic modeling in the centralized control system is realized, as well as functions of protection setting scope shifting, soft strap switching, and protection alarm replacement. The method and process of connecting the protection information to the centralized control system are presented and are proved effective through practice.
出处
《华东电力》
北大核心
2008年第1期47-51,共5页
East China Electric Power
基金
国家电网公司"500kV无人值班变电站研究"
关键词
500
KV变电站
无人值班
监控与保护一体化集控系统
面向保护对象自动建模
500 kV substation
unattended
monitor/protection integrated centralized control system