期刊文献+

热管地板辐射供暖的特性 被引量:9

Thermal Performance of Thermosyphon-Embedded Floor Heating
下载PDF
导出
摘要 在不同的供水温度和流量下对热管地板辐射供暖的特性进行了实验研究.实验结果表明:地板表面温度和散热量随供水温度的升高而明显增加,随流量的增加而略有增加;热管间距为300mm、供水温度为35-45℃、流量为0.1-0.3m^3/h的运行条件下,地板的散热量和表面温度基本可满足供暖房间的需要,供水温度比塑料管系统低4-6℃,管间距比塑料管系统大;地板的蓄热时间是预热时间的3倍左右,与塑料管系统相比具有升温快降温慢的优势;采用热管地板辐射供暖后室内空气竖向温度梯度较小. Thermal performance of hermosyphon-embedded floor heating was investigated at different working conditions. Experimental results indicate that: surface temperature and heat transfer rate of floor increased evidently with the rising of supply water temperature, while they increased slightly with the rising of water flow rate; at the conditions that the distance of thermosyphons is 300 mm, which is greater than that of PPR pipe-embedded floor, the supply water temperature is 35--45 ℃ and the flow rate is 0.1-0.3 m^3/h, surface temperature of the floor is 4--6 ℃ higher than that of PPR pipe-embedded floor; the heat-lag time of the floor is about three times longer than its warm-up time, and the warm-up time of thermosyphon-embedded floor is shorter than that of PPR pipe-embedded floor at the same operating conditions; temperature gradient at the vertical direction in room with ther- mosyphon-embedded floor heating is fairly small.
出处 《天津大学学报》 EI CAS CSCD 北大核心 2007年第10期1209-1214,共6页 Journal of Tianjin University(Science and Technology)
基金 供热 供燃气 通风及空调工程北京市重点实验室开放课题(KF200301)
关键词 热管地板辐射供暖 地板表面散热量 地板表面温度 空气温度分布 预热时间 蓄热时间 Floors Heat transfer Surfaces Temperature distribution
  • 相关文献

参考文献12

  • 1庄骏,张红著..热管技术及其工程应用[M].北京:化学工业出版社,2000:418.
  • 2Zhang Hong,Zhuang Jun.Research,development and industrial application of heat pipe technology in China[J].Applied Thermal Engineering,2003,23 (9):1067-1083. 被引量:1
  • 3张于峰,谢慧,李德英,牛宝联.碳钢-水热虹吸管传热性能的实验研究[J].天津大学学报,2006,39(2):223-228. 被引量:13
  • 4谢慧..热管地板辐射供暖基础理论研究[D].天津大学,2006:
  • 5刘艳峰..地板供暖设计与运行基础理论研究[D].西安建筑科技大学,2004:
  • 6Chen T Y.Application of adaptive predictive control to a floor heating system with a large thermal lag[J].Energy Build,2002,34 (1):45-51. 被引量:1
  • 7Zaheer-uddin M,Zhang Z L,Cho S H.Augmented control strategies for radiant floor heating systems[J].International Journal of Energy Resource,2002,26 (1):79-92. 被引量:1
  • 8Kilkis B I,Eltez M,Sager S S.A simplified model for the design of radiant in-slab heating panels[J].ASHRAE Transactions,1995,101 (1):210-216. 被引量:1
  • 9Kilkis I B,Sapci M.Computer-aided design of radiant subfloor heating systems[J].ASHRAE Transactions,1995,101 (1):1214-1220. 被引量:1
  • 10Oiesen B W.Radiant floor heating in theory and practice[J].Journal of ASHRAE,2002,44 (7):19-26. 被引量:1

二级参考文献17

  • 1Youcef L.Two-dimensional model of direct solar slab on grade heating floor[J].Solar Energy,1991,46(3):183-189. 被引量:1
  • 2Kilkis B ect.A simplified model for the design of radiant in-slab heating panels[J].ASHREA Trans.,1995,101(1):210-216. 被引量:1
  • 3Zhang Hong,Zhuang Jun.Research,development and industrial application of heat pipe technology in China[J].Applied Thermal Engineering,2003,23(9):1067-1083. 被引量:1
  • 4Lee Y,Mital U.A two-phase closed thermosiphon [J].International Journal of Heat Mass Transfer,1972,15:1695-1770. 被引量:1
  • 5Feldman K T Jr,Srinivasan R.Investigation of heat transfer limits in two-phase closed thermosyphon[C]//Proc 5th IHPC.Tuskuba,Japan,1984:192-205. 被引量:1
  • 6Kang Y H,Kang M C,Chun W G.A study on thermal characteristics of the solar collector made with a closed loop thermosyphon [J].International Communications in Heat and Mass Transfer,2003,30(7):955-964. 被引量:1
  • 7Lin Mao-Ching,Chun Lin-Jye,Lee Wen Shing,et al.Thermal performance of a two-phase thermosyphon energy storage system[J].Solar Energy,2003,75 (4):295-306. 被引量:1
  • 8Shiraishi M,Kiiuchi K,Yamanishi T.Investigation of heat transfer characteristics of a two-phase closed thermosyphon[C]//Proc 4th IHPC.London,UK,1981:342-351. 被引量:1
  • 9Imura H,Sasaguchi K,Kozai H.Critical heat flux in a closed two-phase thermosyphon[J].Int J Heat Mass Transfer,1983,26(6):1181-1188. 被引量:1
  • 10Negishi K,Sawada T.Heat transfer performance of an inclined two-phase closed thermosyphon[J].Int J Heat Mass Transfer,1983,26 (8):1207-1213. 被引量:1