摘要 多台FACTS控制器之间的交互影响与协调是FACTS技术应用中亟待解决的问题,介绍了采用相对增益矩阵(RGA)方法,分析了多机电力系统中多台柔性交流输电系统(FACTS)控制器之间的交互影响。通过对4机两区域系统以及新英格兰系统两个实例的分析研究,分别采用频域分析、特征值分析以及时域仿真三种方法来验证RGA所得的结论,证明了RGA方法可以用来分析FACTS间的交互现象。 The paper proposed a method relative gain array(RGA),which is capable of analyzing the interactions among FACTS controllers in multi-machine power system. To demonstrate the comprehensive applications of the presented method , a power system with 4-machine, ll-bus and multi-TCSC, a new England power system with 10-machine ,39-bus installed with SVC and TCSC are investigated . With by non-linear simulation method ,the dynamic interaction among the FACTS controllers is investigated.
作者 李亮
出处 《上海电力》 2007年第6期622-626,共5页 Shanghai Electric Power
关键词 灵活交流输电 静止无功补偿器 可控串补装置 交互影响 相对增益矩阵 Flexible AC Transmission Systems(FACTS) SVC interactions Relative Gain Array( RGA)
  • 相关文献

参考文献10

二级参考文献46

  • 1田杰,尹建华,韩祯祥.TCSC装置的动态特性及其控制策略研究[J].电力系统自动化,1996,20(6):34-36. 被引量:5
  • 2陈淮金.可控串联补偿在提高电力系统稳定性中的作用研究[J].电力系统自动化,1996,20(10):14-17. 被引量:16
  • 3Anderson P M Fouad A A.电力系统的控制与稳定(第一卷)[M].北京:水利电力出版社,1979.. 被引量:1
  • 4Wang, H. F., Interactions and Co-Ordination of Multiple-Function FACTS Controllers, European Transactions on Electrical Power, 11, 7-15, 2001. 被引量:1
  • 5Y.H. Song, A.T. Johns. Flexible AC transmission systems[M].IEE Press, 1999. 被引量:1
  • 6Modelling of power electronics equipment (FACTS) in load flow and stability programs[R]. CIGRE TF 38-01-08, 1998. 被引量:1
  • 7Bristol, E. On a new measure of interaction for multivariable process control [J]. IEEE Trans. Autom. Control AC-11, Jan, 1966: 133-134. 被引量:1
  • 8Mcavoy, Thomas J. Interaction analysis [M]. USA: instrument Society of America 1983. 被引量:1
  • 9Tambey, N. and M. L. Kothari, Damping of Power System Oscillations With Unified Power Flow Controller (UPFC), IEE ProceedingsGeneration Transmission and Distribution, 150, 129-140, 2003. 被引量:1