不接地电力系统中电磁式电压互感器的故障探讨 被引量:1

Discussion on Fault of Electromagnetic Voltage Transformer in Ungrounded Power System
下载PDF
导出
摘要 文章指出了谐振过电压是导致中性点不接地系统电磁式电压互感(TV)出现故障的主要原因。韶关钢铁集团焦化厂抑制过电压的方法有减少TV的运行台数和在6kV系统中实行TV不接地运行。该厂的改造效果明显。文章还提出了其他防止铁磁谐振的方法,如TV中性点处安装消谐器或串接电阻等。 The paper pointed out that resonance over-voltage is the major reason of causing the faults of electromagnetic voltage transformer in ungrounded power system. Guangdong Shaoguan Steel Group adopted the measures to restrain over-voltage,such as reducing the operation number of voltage transformer and ungrounded operation of voltage transformer in 6 kV system. The effect of these measures is obvious. The paper also put forward the other methods for preventing ferro-resonance,such as installing the resonance elimination device or series resistance in neutral point of voltage transformer.
作者 穆应东
出处 《电力设备》 2007年第10期48-49,共2页 Electrical Equipment
关键词 铁磁谐振 不接地系统 电压互感器 ferro-resonance ungrounded system voltage transformer