期刊文献+

小电流接地系统2点异相故障测距法

Fault Location of Two-Point Earth-Fault with Different Phases in Low Earth-Fault Current System
下载PDF
导出
摘要 分析了小电流接地系统中一些典型工况的2点异相接地故障的特点,并运用对称分量原理提出了响应的故障测距算法。这些算法均不受负荷电流、接地故障电阻和消弧线圈(或电阻)的影响,大量的数字防真计算表明,该故障测距算法是可行的。 The characterists of several typical operating conditiongs of two-point earth-fault with different phases in low earth-fault current system are analyzed in this paper,the fault location algorithms based on symmetrical component method are presented.The algorithms can exclude the influences of fault resistance,load current and arc-suppression coil(or resistance).A lot of digital simulation calculations indicate that the fault location algorithms are feasible.
出处 《新技术新工艺》 2007年第8期43-45,共3页 New Technology & New Process
关键词 小电流接地系统 故障测距 算法 2点异相接地故障 low earth-fault current system,fault location,algorithm,two-point earth-fault with different phases
  • 相关文献

参考文献3

  • 1Phadke A G,Hlika T,Ibrahim M,Adamiak M G. A micro-computer based symmetrical component distance relay. proceedings of PICA[J]. IEEE,1979,4. 被引量:1
  • 2Yang Q S et al. Microprocessor-based algorithm for high-resistance earth-fault distance protection[J]. IEE proceedings, 1983,130(6). 被引量:1
  • 3应静良,等.电力系统继电保护与自动化设备手册[M].北京:中国电力出版社,1999. 被引量:1