期刊文献+

双冷源低温系统冷却实验腔的传热分析

Heat transfer analysis of the sample chamber cooled by double-cold-source cryogenic system
下载PDF
导出
摘要 根据双冷源低温系统冷却实验腔的传热特点,建立了二维非稳态传热的数理模型.利用FLUENT计算软件对实验腔的冷却过程进行了数值模拟,得到实验腔底部温度变化曲线和壁面的温度分布,分析了辐射热对实验腔冷却过程的影响.计算结果表明实验腔经过2 h冷却后,底面温度基本稳定在6.27 K,可以满足研究对温度的要求. From the basic heat transfer characters in the sample chamber, the mathematical and physical models of two-dimension unsteady heat transfer were established. The heat conduction of the sample chamber involving the influence of outer radiation heat transfer was numerically simulated by FLUENT. The temperaturedistribution and the temperature variation curve of the sample chamber were obtained. The calculation results indicated that the final temperature of the bottom could reach 6.27 K after 2h, meeting the science research requirement.
出处 《华中科技大学学报(自然科学版)》 EI CAS CSCD 北大核心 2007年第6期96-98,共3页 Journal of Huazhong University of Science and Technology(Natural Science Edition)
基金 国家"十一五"重大科技基础项目
关键词 双冷源 实验腔 非稳态传热 数值模拟 double-cold-source sample chamber unsteady heat transfer numerical simulation
  • 相关文献

参考文献5

  • 1Marshall W S.Development of "fast cool" pulse magnet coil technology at NHMFL[C]//Proceedings of the 7th International Symposium on Research.Toulouse:Elsevier,2004:594-598. 被引量:1
  • 2Steven W,Van Sciver.Cryogenic systems for superconducting devices[J].ELSEVIER Physica C,2001,354:129-135. 被引量:1
  • 3韩占忠,王敬,兰小平.FLUENT流体工程方针计算实例与应用[M].北京:北京理工大学出版社,2004. 被引量:2
  • 4杨强生,浦保荣.高等传热学[M].2版.上海:上海交通大学出版社,1996. 被引量:1
  • 5杨世铭, 陶文铨..传热学[M],1998.