期刊文献+

考虑小水电启停策略的准入容量计算 被引量:11

Penetration Level Calculation Taking into Consideration the Unit Commitment of Small Hydro Power
下载PDF
导出
摘要 随着分布式电源的大力发展,其对原有系统产生了巨大影响。文中以小水电为例,首先分析分布式电源的启停对无功电压控制的影响,然后给出考虑单个分布式电源启停的准入极限功率计算模型。接着分析了多个分布式电源接入系统后,原有的计算模型结果可能过于乐观,提出了多分布式电源接入的至少准入容量的概念,它反映了“最恶劣”机组组合情况下的准入极限功率,并给出了基于主从决策的双层优化模型和求解算法。最后用IEEE 112节点系统的仿真结果证明了模型、算法的有效性。 With the rapid development of distributed generators, the impact on the power system is not to be neglected. Taking small hydro power as an example, this paper firstly analyzes the impact of distributed generators unit commitment on VQC relays. Then a method is proposed for computing the power penetration level taking into account the unit commitment of distributed generators. The above-mentioned model will become overoptimistic when multiple distributed generators are connected into a distribution network. So, the concept of the rain-max penetration level is introduced, that is, the max penetration level under the worst generation pattern. And then, a leader-follower decision-making model based on bi-level optimization is proposed. Finally, a 112-bus test system is utilized to evaluate the proposed model and the results provided.
出处 《电力系统自动化》 EI CSCD 北大核心 2006年第22期48-52,共5页 Automation of Electric Power Systems
基金 国家自然科学基金(50477032) 浙江省电力公司科技项目~~
关键词 分布式电源 机组启停 准入极限功率 双层优化 distributed generator unit commitment penetration level bi-level optimization
  • 相关文献

参考文献23

二级参考文献89

共引文献1725

同被引文献189

引证文献11

二级引证文献338

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部