摘要
为保证热用户的舒适度及节省能源,一些供热工程项目使用气候补偿器,但供热质调节中使用气候补偿器选择调节直(曲)线不合理时,会导致室内舒适度降低及能源浪费,本文做了实例阐述。另外针对国内供热实际中概算热指标偏大系数m和散热器多装面积比L普遍偏大的情况,在质调节中要充分考虑,本文也给出根据实际情况计算m,L的方法,这对于实际供热中在用户舒适度与节能之间找到一个最佳平衡点具有重要意义。
Weather compensators are used to ensure the heat supply engineering projects. But, the uncomfortable comfort level of heat consumer and save energy in some actual level indoor and more energy consumption are generated when selecting an unsuitable regulating Line (or curve) using weather compensators for heating quality regulation. The instances are analyzed based on an example. In addition, the condition of thermal budgetary estimate coefficient m and radiator surface ratio L greater than the actual in quality regulation must be considered adequately, and the method to calculate m and L is given in this article. It is important to ensure the balance between high comfort level and optimum energy utilization for heating project.
出处
《建筑热能通风空调》
2006年第4期67-70,共4页
Building Energy & Environment
关键词
集中质调节
气候补偿器
温度调节直(曲)线
节能
central heating quality regulation, weather compensators, regulating line (or curve) for water-supply temperature, energy-saving