期刊文献+

三种复合玻纤风管法兰连接防冷桥结露实验研究

Experimental research in the condensation performance of three types of glass-fiber composite air duct flange
下载PDF
导出
摘要 归纳并设计F型、T型和J型三种复合玻纤风管法兰,通过自制的实验装置对它们的温度及J型管道表面温度进行测试,分析了J型法兰温度随环境温度及风管内气流温度的变化规律和J型法兰风管表面温度的分布状况。结果表明J型法兰不会结露,其性能优于F型及T型法兰。 Sums up and designs three kinds of glass-fiber composite air duct flanges, F-type, T-type and J-type, tests their temperature and air duct surface temperature of J-type. Analyses the behavior of J-type flange temperature changing with ambient temperature and air temperature in duct, presents the temperature distribution pattern of the air duct with J-type flange, The results show that only J-type flange can not produce condense water, it is much better than the F- and T-type flange.
机构地区 南京工业大学
出处 《暖通空调》 北大核心 2006年第1期129-131,86,共4页 Heating Ventilating & Air Conditioning
关键词 复合玻纤风管 J型法兰 T型法兰 F型法兰 结露性能 实验研究 glass-fiber composite air duct, J-type flange, T-type flange, F-type flange, condensation performance, experimental research
  • 相关文献

参考文献5

  • 1周鹏晨,严俊.复合铝箔玻璃纤维风管性能剖析[J].暖通空调,1999,29(4):76-78. 被引量:8
  • 2叶晓江,张明宏,刘庆中.复合玻纤板风管[J].建筑热能通风空调,1999,18(3):61-62. 被引量:3
  • 3陆耀庆主编..实用供热空调设计手册[M].北京:中国建筑工业出版社,1993:1256.
  • 4赵荣义等编..空气调节 第3版[M].北京:中国建筑工业出版社,1994:303.
  • 5中国有色工程设计研究总院.GB 50019-2003采暖通风与空气调节设计规范[S].北京:中国计划出版社,2004.. 被引量:17

二级参考文献5

  • 1毛建素,暖通空调,1998年,28卷,4期 被引量:1
  • 2龚崇实,全国通风管道制作安装手册,1986年 被引量:1
  • 3孙万钢,建筑声学设计,1979年 被引量:1
  • 4Johns Manville 公司,HVAC风管设计指南 被引量:1
  • 5空调国际有限公司(AHSI中国),风管系统暖通空调主件风管定制专业保温材料产品样本 被引量:1

共引文献24

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部