结合目前电网运行方式,分析了哈南主变停电给电网运行带来的影响,制定了解决措施,切实保证了电网的安全稳定运行,并提出了哈南变增设第二组变压器的建议。
The effect if the main transformer failed on the power grid operation was analyzed according to the power grid operation mode at present, the countermeasures to this situation were made, which will ensure the power net to run safely and steadily, and the suggestion to set up one more main transformer in Hanan substation was put forward in the paper.
出处
《黑龙江电力》
CAS
2005年第5期354-356,共3页
Heilongjiang Electric Power
关键词
500KV变电所
运行方式
潮流计算
控制措施
供电可靠性
500 kV substation
operation mode
powflow calculation
control measure
reliability of power supply