发变组保护双重化过程中的几个问题与反思 被引量:1

Analysis of dual configuration for generator-transformer group unit protection
下载PDF
导出
摘要 针对25条反措提出的保护配置双重化问题,结合扬州二电厂2*600 MW进口机组及相关电厂发变组保护装置的安装和运行,对一些现实工作中存在的误区作一分析与总结,并对更好地执行25条反措提出了相关建议。 This paper introduced the dual configuration fro generator-transformer group unit protection required by the “The 25 antiaccidents protection regulations in electric power industry”. Setting and operation of generator-transformer group unit protection for 2 · 600 MW units in Yangzhou No. 2 Power Generation Co. ,Ltd, was related. And in other plants alike, this paper analyzed some misleading points existed in practical application and gave some advice on The Regulation's Transaction executing.
作者 黄勇 周又可
出处 《继电器》 CSCD 北大核心 2005年第16期14-16,共3页 Relay
关键词 发变组保护 25条反措 保护双重化 generator-transformer group unit protection the 25 anti-accidents protection regulations in electric power industry protection dual configuration