According to in-situ monitoring data, the displacement of rock slope varies with time, and the variation of air temperature is doubted to be one of the influencing factors. Through the calculation of the temperature and displacement fields for the rock slope of the powerhouse of the Geheyan Hydropower Station, it is found that the influence of air temperature on the displacement of the slope is only in the range of several millimeters, while the fluctuation of measured displacement is in the range of several centimeters; besides, the fluctuation of calculated displacement is annually changed, while the variation of measured displacement shows no obvious periodicity. Therefore, the variation of air temperature is not the main factor affecting the displacement of the slope. Moreover, some regularities about the displacement varying with air temperature are also found through calculation: the variation of displacement lags behind that of air temperature for 35-75 days; the influence of air temperature on rock mass can reach a depth of 10 m; the steady temperature of rock mass is about 17?℃, etc.