期刊文献+

湿工况下冷却空气型干式蒸发器盘管的数值模拟和性能优化 被引量:2

NUMERICAL SIMULATION AND PERFORMANCE OPTIMIZATION FOR AIR-COOLING DRY EVAPORATOR COIL IN WET CONDITION
下载PDF
导出
摘要 本文采用分布参数法对湿工况下冷却空气型干式蒸发器盘管进行了数值模拟,在空气相对湿度从15 %到85 %的变化范围内分析了反映蒸发器盘管性能的各种参数的变化规律。研究表明,空气相对湿度对蒸发器盘管的换热性能影响很大。当空气相对湿度高于6 8.1%时,蒸发器潜热吸热量将大于显热吸热量,送风温度升高。本文提出了优化蒸发器盘管换热性能的一些措施,在压降的约束条件下。 In this paper, a distributed parameter model for predicting air-cooling dry evaporator coil is derived. The model uses numerical method to analyze the regulation of many parameters which reflect the performance of evaporator coil under diverse relative humidity ranging from 15% to 85%. The study shows that the air relative humidity significantly affects the performance of the evaporator coil. When the relative humidity of inflow air is greater than 68.1%, the latent cooling load will be more than the sensible cooling load, and outflow air temperature will rise. Furthermore, some measures are developed to optimize the total performance of evaporator coil. To properly change the refrigerant mass flow rate could reach the optimum solution of coil performance with constraint condition of pressure drop.
出处 《制冷与空调》 2005年第2期19-24,共6页 Refrigeration and Air-Conditioning
关键词 湿工况 冷却空气 干式蒸发器盘管 数值模拟 性能优化 空调 Evaporator coil Wet condition Heat transfer performance Optimization
  • 相关文献

参考文献10

  • 1葛云亭,彦启森.蒸发器动态参数数学模型的建立与理论计算[J].制冷学报,1995,17(1):9-17. 被引量:38
  • 2刘志刚等编著..工质热物理性质计算程序的编制及应用[M].北京:科学出版社,1992:376.
  • 3Jia X, Tso C P, Jolly P et al. Distributed steady and dynamic modeling of dry- expansion evaporators[Jl. International Journal of Refrigeration, 1999, 22 : 126-136. 被引量:1
  • 4Liang S Y, Liu T N, Wong T Net al. Analytical study of evaporator coil in humid environment[J]. Applied Thermal Engineering, 1999, 19: 1129-1145. 被引量:1
  • 5左潞..空调用直接蒸发式空气冷却器的数值模拟及空气来流不均匀性对其影响分析[D].西安交通大学,1990:
  • 6Yun Rin, Kim Y C. A generalized correlation for evaporation heat transfer of refrigerants in micro- fin tubes[J]. International Journal of Refrigeration, 2002, 45 : 2003-2010. 被引量:1
  • 7Wang H S, Rose J W, Honda H. Condensation of refrigerants in horizontal micro- fin tubes:comparison of correlations of frictional pressure drop[J]. International Journal of Refrigeration, 2003, 26; 461- 472. 被引量:1
  • 8Paliwoda Aleksander. Generalized method of pressure drop calculation across pipe components containing two phase flow of refrigerants[J]. International Journal of Refrigeration, 1992, 15: 119-125. 被引量:1
  • 9Wang C C, Hwang Y M, Lin Y T. Empirical correlations for heat transfer and flow friction characteristics of herringbone wavy fin - and - tube heat exchanger[J]. International Journal of Refrigeration, 2002, 25 : 673-680. 被引量:1
  • 10Domanski P A. Simulation of an evaporator with nonuniform one dimensional air distribution[J]. ASHRAE Transactions,1991, 2; 793-797. 被引量:1