发电机定子线棒绝缘老化后不同部位参数比较 被引量:6

STUDY ON AGING STATE OF WINDING INSULATION IN DIFFERENT POSITION BY SEVERAL METHODS
下载PDF
导出
摘要 分别测量与研究了大型发电机主绝缘的槽部、出槽口和端部这 3个不同部位的真机线棒绝缘的tanδ、超声声速、动态力学参数和绝缘强度等 4种参数。试验研究发现出槽口附近的主绝缘老化最为严重 。 Ground-wall insulation of end-windings, ground-wall insulation in the slots and ground-wall insulation between above two positions have been obtained from a large generator that has been operated 18 years. Several parameters (tan δ , ultrasonic detecting, DMA, dielectric strength) of the above three positions of the samples have been tested and studied. The test results show that the aging extent of ground-wall insulation between end-windings and the slots 1s the most serious. This conclusion is important in maintenance of large generator and estimating aging state of ground-wall insulation.
出处 《高电压技术》 EI CAS CSCD 北大核心 2004年第5期23-24,49,共3页 High Voltage Engineering
关键词 大型发电机 定子线棒 绝缘老化 绝缘强度 动态力学分析 aging state ultrasonic detecting DMA dielectric strength
  • 相关文献

参考文献4

二级参考文献26

  • 1宋建成.大电机主绝缘多因子老化特征参量的研究[M].西安:西安交通大学,1999.. 被引量:1
  • 2顾振军 于威廉.电介质化学[M].北京:机械工业出版社,1989.. 被引量:1
  • 3[1]Stone G C,Sedding H G,Lloyd B A,et al.The ability of diagnostic tests to estimate the remaining life of stator insulation.IEEE Trans.on Energy Conversion,1988,3(4)∶833~841 被引量:1
  • 4[2]Kim Y J,Nelson J K.Assessment of deterioration in epoxy mica machine insulation.IEEE Trans.on Electrical Insulation,1992,27(5)∶1026~1039 被引量:1
  • 5[3]Gupta B K,Culbert I M.Assessment of insulation condition in rotating machine stators.IEEE Trans.on Energy Conversion,1992,7(3)∶500~508 被引量:1
  • 6[4]Kimura K,Kaneda Y.The role of microscopic defects in multistress aging of micaceous insulation.IEEE Trans.on Dielectrics and Electrical Insulation,1995,2(3)∶426~432 被引量:1
  • 7[5]James R E,Phung B T.Development of computer-based measurements and their application to PD pattern analysis.IEEE Trans.on Dielectrics and Electrical Insulation,1995,2(5)∶838~855 被引量:1
  • 8[6]Gulski E.Digital analysis of partial discharges.IEEE Trans. on Dielectrics and Electrical Insulation,1995,2(5)∶822~837 被引量:1
  • 9[7]Morshuis P.Assessment of dielectric degradation by ultrawide-band PD detection.IEEE Trans. on Dielectrics and electrical insulation,1995,2(5)∶744~760 被引量:1
  • 10[8]Yin Zhide,Tan Kexiong,Wang Zhongdong,et al.Recognition of partial discharge in stator winding models based on 3-demensional pattern using artificial neural network.Proceedings of International Conference on Power System Technology,POWERCON' 98,1998,2∶1054~1057 被引量:1

共引文献32