期刊文献+

谐波电场法带电检测直流绝缘子 被引量:5

Harmonic Electric Field Method for Live Detecting DC Insulator
下载PDF
导出
摘要 挂网运行的直流绝缘子数量越来越多,其检测问题日益突出。分析认为,合成绝缘子内导通性故障及零值瓷绝缘子是最难发现、最危险的故障。文中研究了这类故障直流绝缘子的带电检测问题,提出利用直流绝缘子串周围谐波电场带电检测直流绝缘子的新方法,即谐波电场法,并进行了可行性试验与灵敏度分析。现场与实验室可行性试验表明,谐波电场法能够对直流绝缘子进行在线检测。理论分析表明,该方法灵敏度较高,能有效地给出低于一定阻值的零值瓷绝缘子和合成绝缘子内绝缘导通性故障信息。谐波电场法的提出为直流绝缘子带电检测提供了有力手段。 It is more and more important to detect the DC insulators because insulators have been coming into use in plenty in power systems. Analyses indicate that the internal insulation defects of composite insulators and the low resistance faults of porcelain insulators are very dangerous and also difficult to be detected. The paper discusses the problem above and proposes a novel method, viz. harmonic electric field method, which utilizes the harmonic electric field distribution of DC insulator to live detect DC ...
出处 《电力系统自动化》 EI CSCD 北大核心 2005年第15期63-67,共5页 Automation of Electric Power Systems
基金 国家自然科学基金资助项目(90210015)。~~
关键词 直流绝缘子 带电检测 谐波电场法 DC insulator live detection harmonic electric field method
  • 相关文献

参考文献5

  • 1[1]VAILLANCOURT G H, BELLERIVE J P, ST-JEAN M et al.New Live Line Tester for Porcelain Suspension Insulators on High-voltage Power Lines. IEEE Trans on Power Delivery,1994, 9(1): 208-220. 被引量:1
  • 2[2]VAILLANCOURT G H, BELLERIVE J P, JEAN C.Experience with the Detection of Faulty Compositors on Highvoltage Power Lines by the Electric Field Measurement Method.IEEE Trans on Power Delivery, 1998, 13(2): 661-667. 被引量:1
  • 3[8]JIANG Xiu-chen, LU Zhong-liang, HAN Zhen-dong. A New Measuring Method and Characteristic of HVDC Insulator Voltage Distribution. In: Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, Vol 2. Xi'an(China): 2000. 1019-1022. 被引量:1
  • 4[9]TRAIN D, DUBE R. Measurements of Voltage Distributions on Suspension Insulators for HVDC Transmission Lines. IEEE Trans on Power Apparatus and Systems, 1983, 102 (8):2461-2475. 被引量:1
  • 5[10]ZHAO Tie-bin, COMBER M G. Calculation of Electric Field and Potential Distribution Along Nonceramic Insulators Considering the Effects of Conductors and Transmission Towers. IEEE Trans on Power Delivery, 2000, 15(1): 313-319. 被引量:1