For a large-scale high voltage direct current (HVDC)asynchronous interconnected power grid, the frequency issue atthe power sending side under DC faults is a crucial problem.To solve this problem, based on rotor motio...For a large-scale high voltage direct current (HVDC)asynchronous interconnected power grid, the frequency issue atthe power sending side under DC faults is a crucial problem.To solve this problem, based on rotor motion equations, theeffect of unbalanced power on the system frequency under DCfaults is analyzed. The characteristics and dynamic developmentprocess of frequencies after the injection of disturbances areanalyzed. In addition, the actions and coordinated strategies ofvarious frequency control measures are also investigated. Basedon the testing projects of an asynchronous interconnection in theChina Southern Power Grid (CSG), the frequency features arestudied according to the measured PMU data. The outcome showsthat the frequency problem of the Yunnan Power Grid after anasynchronous interconnection can be solved and controlled. Italso shows that the frequency limit control (FLC) is importantfor the frequency regulation of large scale HVDC asynchronousinterconnected DC power grids. As demonstrated, DC FLC caneffectively suppress the deviation of the transient frequency.However, reasonable frequency regulation parameters shouldbe set and other area frequency control measures should becoordinated to maintain the frequency stability of the system.展开更多
电力电缆在运行中出现检修或故障时,需要短时转移负荷,致使某些电缆短时过载。然而电缆允许过载电流极限与过载电流持续时间之间的关系缺乏相应算法及成熟标准支持,使得现场紧急转移负荷时没有可靠依据。文中根据集中热常数模型和IEC 60...电力电缆在运行中出现检修或故障时,需要短时转移负荷,致使某些电缆短时过载。然而电缆允许过载电流极限与过载电流持续时间之间的关系缺乏相应算法及成熟标准支持,使得现场紧急转移负荷时没有可靠依据。文中根据集中热常数模型和IEC 60853模型2种暂态热路模型,研究了相应的短时过载电流极限及其持续时间的计算原理,并针对64/110 k V YJLW02单芯高压电缆进行了具体敷设的分析和比较,结果表明:基于2种模型的关系曲线变化趋势相近,但IEC 60853模型法更接近实际情况。计算方法可为电缆短时转移负荷的决策提供参考和指导。展开更多
文摘For a large-scale high voltage direct current (HVDC)asynchronous interconnected power grid, the frequency issue atthe power sending side under DC faults is a crucial problem.To solve this problem, based on rotor motion equations, theeffect of unbalanced power on the system frequency under DCfaults is analyzed. The characteristics and dynamic developmentprocess of frequencies after the injection of disturbances areanalyzed. In addition, the actions and coordinated strategies ofvarious frequency control measures are also investigated. Basedon the testing projects of an asynchronous interconnection in theChina Southern Power Grid (CSG), the frequency features arestudied according to the measured PMU data. The outcome showsthat the frequency problem of the Yunnan Power Grid after anasynchronous interconnection can be solved and controlled. Italso shows that the frequency limit control (FLC) is importantfor the frequency regulation of large scale HVDC asynchronousinterconnected DC power grids. As demonstrated, DC FLC caneffectively suppress the deviation of the transient frequency.However, reasonable frequency regulation parameters shouldbe set and other area frequency control measures should becoordinated to maintain the frequency stability of the system.
文摘电力电缆在运行中出现检修或故障时,需要短时转移负荷,致使某些电缆短时过载。然而电缆允许过载电流极限与过载电流持续时间之间的关系缺乏相应算法及成熟标准支持,使得现场紧急转移负荷时没有可靠依据。文中根据集中热常数模型和IEC 60853模型2种暂态热路模型,研究了相应的短时过载电流极限及其持续时间的计算原理,并针对64/110 k V YJLW02单芯高压电缆进行了具体敷设的分析和比较,结果表明:基于2种模型的关系曲线变化趋势相近,但IEC 60853模型法更接近实际情况。计算方法可为电缆短时转移负荷的决策提供参考和指导。