Entropy Analysis of NH_3/H_2O Absorption-Compression Heat Pump 被引量:1
1
作者 龙臻 罗勇 +2 位作者 田永军 廉永旺 马伟斌 《Journal of Donghua University(English Edition)》 EI CAS 2012年第6期461-464,共4页
The absorption-compression heat pump (ACHP) has been considered as an effective approach to recover and utilize low-grade heat sources. In the present study, the first and second law thermodynamic analyses of the AC... The absorption-compression heat pump (ACHP) has been considered as an effective approach to recover and utilize low-grade heat sources. In the present study, the first and second law thermodynamic analyses of the ACHP with NH3/H20 as working fluid were performed. Thermodynamic properties of each point and heat transfer rate of each component in the cycle under basic operation conditions were calculated from the first law analysis. Following the second law of thermodynamics, the entropy generation of each component and the total entropy generation of the system were obtained. The effect~ of the heating temperature, heat source temperature, and compression ratio on the coefficient of performance (COP) and the total entropy generation ( STot ) of the system were examined. The results show that the increase in COP corresponds to a decrease in STot, and vice versa; besides, for certain operating conditions, an optimum compression ratio in the NH~/H20 ACHP exists. 展开更多
关键词 heat pump absorption-compression second law ofthermodynamics entropy generation