This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)g...This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)grid.The DC CFC consists of two identical full bridge DC-DC converters with the capacitors of the two converters being connected in parallel.The scalability of the DC CFC is easily achievable due to the identical bridge converter topology;the cost of this DC CFC is also relatively low due to its simple physical structure and low voltage ratings.The control performance of the DC CFC is tested on a meshed 3-terminal(3-T)HVDC grid,which is based on modular multilevel converters(MMC).The DC branch current control in the meshed MTDC grid is achieved using the proposed control strategy of the DC CFC,and is verified through case studies on the real-time digital simulator(RTDS).展开更多
Full-Bridge Modular Multilevel Converter(FBMMC) has strong ability to ride through serious DC faults,thus it is very suitable for multi-terminal flexible HVDC applications.However,no references have reported the locat...Full-Bridge Modular Multilevel Converter(FBMMC) has strong ability to ride through serious DC faults,thus it is very suitable for multi-terminal flexible HVDC applications.However,no references have reported the locating and isolating of DC faults and corresponding DC faults ride-through capability evaluation index.This paper introduces the topology mechanism of FBMMC and its loss reduction operation mode,theoretically certifies that the universal decoupled control strategy of Voltage Source Converter(VSC) and the similar modulation strategies of Half-Bridge MMC(HBMMC) can be applied to FBMMC for constructing complete closed-loop control system.On the basis of the existing DC faults locating and isolating schemes of 2-level VSC based Multi-Terminal HVDC(VSC-MTDC) system and the particularity of FBMMC,this paper proposes the DC faults wire selection "handshaking" method of the FBMMC-MTDC system,and proposes the DC Fault Ride-Through Capability Index(DFRTI) for evaluating the DC faults suppressing capability of the VSC-MTDC systems,including FBMMC-MTDC.Simulations of FBMMC-MTDC in PSCAD/EMTDC validate the correctness and effectiveness of the proposed control strategy and evaluation index.展开更多
DC fault protection is the key technique for the development of the DC distribution and transmission system. This paper analyzes the transient characteristics of DC faults in a modular multilevel converter(MMC) based ...DC fault protection is the key technique for the development of the DC distribution and transmission system. This paper analyzes the transient characteristics of DC faults in a modular multilevel converter(MMC) based DC system combining with the numerical method. Meanwhile,lots of simulation tests based on MATLAB/Simulink are carried out to verify the correctness of the theoretical analysis. Finally, the technological difficulties of and requirements for the protection and isolation are discussed to provide the theoretical foundation for the design of dc fault protection strategy.展开更多
This paper investigates a control and protection strategy for a four-terminal modular multilevel converter(MMC)based high-voltage direct current(HVDC)system under a converter-side AC fault.Based on the system operatin...This paper investigates a control and protection strategy for a four-terminal modular multilevel converter(MMC)based high-voltage direct current(HVDC)system under a converter-side AC fault.Based on the system operating condition,a control and protection strategy against the fault with normal blocking of the converter is proposed.In practical,applications encountering such a fault,the MMC at the fault side may experience different conditions of blocking failure.The blocking failures may occur on:①the whole converter;②one converter arm;③one sub-module(SM)/several SMs of one converter arm;④other conditions.The phenomenon of the multi-terminal HVDC(MTDC)system following the fault is analyzed under the first three conditions with real-time simulations using the real-time digital simulator(RTDS).Based on the impact of different conditions on the MTDC system,the necessity of utilizing special control and protection is discussed.A special control and protection strategy is proposed for emergency conditions,and its effectiveness is verified by real-time simulation results.展开更多
基金supported by UK-China Smart Grid Project ERIFT via UK EPSRC,University of Birmingham SiGuang Li Scholarship and China Scholarship Council。
文摘This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)grid.The DC CFC consists of two identical full bridge DC-DC converters with the capacitors of the two converters being connected in parallel.The scalability of the DC CFC is easily achievable due to the identical bridge converter topology;the cost of this DC CFC is also relatively low due to its simple physical structure and low voltage ratings.The control performance of the DC CFC is tested on a meshed 3-terminal(3-T)HVDC grid,which is based on modular multilevel converters(MMC).The DC branch current control in the meshed MTDC grid is achieved using the proposed control strategy of the DC CFC,and is verified through case studies on the real-time digital simulator(RTDS).
基金supported by the National Natural Science Foundation of China (Grant No. 51177042)the Key Project of the National Twelfth FiveYear Research Program of China (Grant No. 2010BAA01B01)
文摘Full-Bridge Modular Multilevel Converter(FBMMC) has strong ability to ride through serious DC faults,thus it is very suitable for multi-terminal flexible HVDC applications.However,no references have reported the locating and isolating of DC faults and corresponding DC faults ride-through capability evaluation index.This paper introduces the topology mechanism of FBMMC and its loss reduction operation mode,theoretically certifies that the universal decoupled control strategy of Voltage Source Converter(VSC) and the similar modulation strategies of Half-Bridge MMC(HBMMC) can be applied to FBMMC for constructing complete closed-loop control system.On the basis of the existing DC faults locating and isolating schemes of 2-level VSC based Multi-Terminal HVDC(VSC-MTDC) system and the particularity of FBMMC,this paper proposes the DC faults wire selection "handshaking" method of the FBMMC-MTDC system,and proposes the DC Fault Ride-Through Capability Index(DFRTI) for evaluating the DC faults suppressing capability of the VSC-MTDC systems,including FBMMC-MTDC.Simulations of FBMMC-MTDC in PSCAD/EMTDC validate the correctness and effectiveness of the proposed control strategy and evaluation index.
基金supported by the National High Technology Research and Development Program of China(863 Program)(No.2015AA050101)the National Science Fund for Excellent Young Scholars(No.51422703)
文摘DC fault protection is the key technique for the development of the DC distribution and transmission system. This paper analyzes the transient characteristics of DC faults in a modular multilevel converter(MMC) based DC system combining with the numerical method. Meanwhile,lots of simulation tests based on MATLAB/Simulink are carried out to verify the correctness of the theoretical analysis. Finally, the technological difficulties of and requirements for the protection and isolation are discussed to provide the theoretical foundation for the design of dc fault protection strategy.
基金This work is supported by UK EPSRC and UK National Grid.
文摘This paper investigates a control and protection strategy for a four-terminal modular multilevel converter(MMC)based high-voltage direct current(HVDC)system under a converter-side AC fault.Based on the system operating condition,a control and protection strategy against the fault with normal blocking of the converter is proposed.In practical,applications encountering such a fault,the MMC at the fault side may experience different conditions of blocking failure.The blocking failures may occur on:①the whole converter;②one converter arm;③one sub-module(SM)/several SMs of one converter arm;④other conditions.The phenomenon of the multi-terminal HVDC(MTDC)system following the fault is analyzed under the first three conditions with real-time simulations using the real-time digital simulator(RTDS).Based on the impact of different conditions on the MTDC system,the necessity of utilizing special control and protection is discussed.A special control and protection strategy is proposed for emergency conditions,and its effectiveness is verified by real-time simulation results.