柜式气体绝缘开关设备(cubicle gas insulatedswitchgear,C-GIS)由于其全可靠性能高、小型化等特点在电力系统中得到广泛的应用。但由于C-GIS开关柜的主要绝缘介质SF6气体具有较强的温室效应,且其成本较高,迫切需要减少或不用SF6气体。...柜式气体绝缘开关设备(cubicle gas insulatedswitchgear,C-GIS)由于其全可靠性能高、小型化等特点在电力系统中得到广泛的应用。但由于C-GIS开关柜的主要绝缘介质SF6气体具有较强的温室效应,且其成本较高,迫切需要减少或不用SF6气体。针对C-GIS开关柜较低的气压条件,探讨SF6混合气体替代SF6的可行性。采用圆形平板电极模拟均匀场,研究均匀场、较低气压(0.1~0.25 MPa)下SF6与N2、CO2两种气体的二元混合气体在不同配比、不同电压形式(工频和负极性雷电冲击)作用下的击穿特性。试验结果表明,气压在0.25 MPa以下时,适当增大SF6混合气体的压强可以使其达到纯SF6相同的绝缘强度,为新型C-GIS开关柜的设计制造提供了关键的试验依据。展开更多
CF3I has been widely considered as a potential alternative for SF6,because it has low global warming potential(GWP)but an insulation capability that is 1.2 times greater than that of SF6.In this paper,the electron swa...CF3I has been widely considered as a potential alternative for SF6,because it has low global warming potential(GWP)but an insulation capability that is 1.2 times greater than that of SF6.In this paper,the electron swarm parameters of CF3I and its gas mixture with N2,including the effective ionization coefficient and electron drift velocity,are examined theoretically through the Boltzmann equation method in the condition of steady-state Townsend(SST)experiments.Based on the derived data of the limiting field strength of CF3I-N2gas mixture,taking into consideration of environmental aspects such as GWP,ozone depletion potential(ODP),liquefaction temperature and toxicity,we studied the possibility of applying the gas mixture as the insulation medium in gas-insulated switchgears(GIS)or cubic type gas-insulated switchgears(C-GIS).It is found that CF3I-N2gas mixtures contained 30%~70%CF3I perform comprehensively better than pure SF6and compressed N2,and especially in medium and low voltage environments,the boiling point of CF3I-N2gas mixture meets the domestic and global requirements in mid-low latitude regions.Therefore we conclude that the gas mixture is acceptable for replacing SF6as the insulation medium in C-GISs.展开更多
文摘柜式气体绝缘开关设备(cubicle gas insulatedswitchgear,C-GIS)由于其全可靠性能高、小型化等特点在电力系统中得到广泛的应用。但由于C-GIS开关柜的主要绝缘介质SF6气体具有较强的温室效应,且其成本较高,迫切需要减少或不用SF6气体。针对C-GIS开关柜较低的气压条件,探讨SF6混合气体替代SF6的可行性。采用圆形平板电极模拟均匀场,研究均匀场、较低气压(0.1~0.25 MPa)下SF6与N2、CO2两种气体的二元混合气体在不同配比、不同电压形式(工频和负极性雷电冲击)作用下的击穿特性。试验结果表明,气压在0.25 MPa以下时,适当增大SF6混合气体的压强可以使其达到纯SF6相同的绝缘强度,为新型C-GIS开关柜的设计制造提供了关键的试验依据。
基金Project supported by National Natural Science Foundation of China (51177101)
文摘CF3I has been widely considered as a potential alternative for SF6,because it has low global warming potential(GWP)but an insulation capability that is 1.2 times greater than that of SF6.In this paper,the electron swarm parameters of CF3I and its gas mixture with N2,including the effective ionization coefficient and electron drift velocity,are examined theoretically through the Boltzmann equation method in the condition of steady-state Townsend(SST)experiments.Based on the derived data of the limiting field strength of CF3I-N2gas mixture,taking into consideration of environmental aspects such as GWP,ozone depletion potential(ODP),liquefaction temperature and toxicity,we studied the possibility of applying the gas mixture as the insulation medium in gas-insulated switchgears(GIS)or cubic type gas-insulated switchgears(C-GIS).It is found that CF3I-N2gas mixtures contained 30%~70%CF3I perform comprehensively better than pure SF6and compressed N2,and especially in medium and low voltage environments,the boiling point of CF3I-N2gas mixture meets the domestic and global requirements in mid-low latitude regions.Therefore we conclude that the gas mixture is acceptable for replacing SF6as the insulation medium in C-GISs.