The static voltage stability of the power system integrating wind farms adopting different kinds of wind turbines is analyzed. Through the simulation of one certain local power grid in Xinjiang Uygur Autonomous Region...The static voltage stability of the power system integrating wind farms adopting different kinds of wind turbines is analyzed. Through the simulation of one certain local power grid in Xinjiang Uygur Autonomous Region, the PV curves at the point of common coupling (PCC), key buses and important substations are plotted; the variation of voltage as well as the limit and margin of static stability are analyzed. It is resulted from the simulation that the limit of static voltage at weak nodes is lower, and the static voltage of the power system with wind farms adopting doubly-fed induction generators (DFIG) is more stable than that with wind farms adopting common asynchronous generators.展开更多
随着新能源电力的蓬勃发展,中国西北地区的高压直流送端系统逐渐呈现出新能源占比高、交流网架薄弱、转动惯量小等特征,由此引发的弱送端系统电压稳定性问题不容忽视。首先,从含大规模光伏并网的弱送端换流母线静态电压调节灵敏度出发,...随着新能源电力的蓬勃发展,中国西北地区的高压直流送端系统逐渐呈现出新能源占比高、交流网架薄弱、转动惯量小等特征,由此引发的弱送端系统电压稳定性问题不容忽视。首先,从含大规模光伏并网的弱送端换流母线静态电压调节灵敏度出发,推导了影响换流母线电压稳定性的因素。进而设计了光伏并网临界容量的计算流程,为光伏场站选址定容提供依据。提出了送端综合短路比指标(sending-end comprehensive short circuit ratio,SCSCR),用来描述含大规模光伏并网的弱送端交流系统的支撑强度。比较了SCSCR、短路比、有效短路比等指标,结果表明SCSCR与弱送端系统静态电压稳定性更具相关性。SCSCR指标可以简化弱送端系统电压稳定性的分析过程,指导高比例新能源外送系统的电源组织与拓扑设计。展开更多
基金National Natural Science Foundation of China(5076700350867004)Autonomous university research projects(XJEDU2007105)
文摘The static voltage stability of the power system integrating wind farms adopting different kinds of wind turbines is analyzed. Through the simulation of one certain local power grid in Xinjiang Uygur Autonomous Region, the PV curves at the point of common coupling (PCC), key buses and important substations are plotted; the variation of voltage as well as the limit and margin of static stability are analyzed. It is resulted from the simulation that the limit of static voltage at weak nodes is lower, and the static voltage of the power system with wind farms adopting doubly-fed induction generators (DFIG) is more stable than that with wind farms adopting common asynchronous generators.
文摘随着新能源电力的蓬勃发展,中国西北地区的高压直流送端系统逐渐呈现出新能源占比高、交流网架薄弱、转动惯量小等特征,由此引发的弱送端系统电压稳定性问题不容忽视。首先,从含大规模光伏并网的弱送端换流母线静态电压调节灵敏度出发,推导了影响换流母线电压稳定性的因素。进而设计了光伏并网临界容量的计算流程,为光伏场站选址定容提供依据。提出了送端综合短路比指标(sending-end comprehensive short circuit ratio,SCSCR),用来描述含大规模光伏并网的弱送端交流系统的支撑强度。比较了SCSCR、短路比、有效短路比等指标,结果表明SCSCR与弱送端系统静态电压稳定性更具相关性。SCSCR指标可以简化弱送端系统电压稳定性的分析过程,指导高比例新能源外送系统的电源组织与拓扑设计。