In this article, the low pressure axial flow fan with circumferential skewed rotor blade, including the radial blade, the forward-skewed blade and the backward-skewed blade, was studied with experimental methods. The ...In this article, the low pressure axial flow fan with circumferential skewed rotor blade, including the radial blade, the forward-skewed blade and the backward-skewed blade, was studied with experimental methods. The aerodynamic performance of the rotors was measured. At the design condition at outlet of the rotors, detailed flow measurements were performed with a five-hole probe and a Hot-Wire Anemometer (HWA). The results show that compared to the radial rotor, the forward-skewed rotor demonstrates a wider Stable Operating Range (SOR), is able to reduce the total pressure loss in the hub region and make main loading of blade accumulating in the mid-span region. There is a wider wake in the upper mid-span region of the forward-skewed rotor. Compared to the radial rotor, in the backward-skewed rotor there is higher total pressure loss near the hub and shroud regions and lower loss in the mid-span region. In addition, the velocity deficit in the wake is lower at mid-span of the backward-skewed rotor than the forward-skewed rotor.展开更多
基金supported by the National Natural Science Foundation of China (Grant No.50406017).
文摘In this article, the low pressure axial flow fan with circumferential skewed rotor blade, including the radial blade, the forward-skewed blade and the backward-skewed blade, was studied with experimental methods. The aerodynamic performance of the rotors was measured. At the design condition at outlet of the rotors, detailed flow measurements were performed with a five-hole probe and a Hot-Wire Anemometer (HWA). The results show that compared to the radial rotor, the forward-skewed rotor demonstrates a wider Stable Operating Range (SOR), is able to reduce the total pressure loss in the hub region and make main loading of blade accumulating in the mid-span region. There is a wider wake in the upper mid-span region of the forward-skewed rotor. Compared to the radial rotor, in the backward-skewed rotor there is higher total pressure loss near the hub and shroud regions and lower loss in the mid-span region. In addition, the velocity deficit in the wake is lower at mid-span of the backward-skewed rotor than the forward-skewed rotor.