In order to obtain reasonable schemes of arrester in converter stations, the arrester scheme of "Xiluodu-Guangdong HVDC ± 500 kV double circuit transmission" project against lighting induced overvoltage...In order to obtain reasonable schemes of arrester in converter stations, the arrester scheme of "Xiluodu-Guangdong HVDC ± 500 kV double circuit transmission" project against lighting induced overvoltage, which was designed according to the main principle of lightning protection in converter station, is discussed. A calculation of the lighting induced overvoltage in Zhaotong converter station un- der various operation modes is performed with ATP-EMTP software, then the surge arrester configuration of the converter station is decided, and the arrester protection schemes of smoothing reactor and neutral line are studied. It is concluded that additional protection is necessary because of the relatively large gap between protected disconnecting switch and arrester of metallic return transfer bus. Plus, the smoothing reactor (SR) arrester near the valve hall could be removed to improve the scheme’s economic performance.展开更多
开展输电线路耐雷水平影响因素的研究是科学的输电线路防雷设计的基础。由于我国规程规定,35 k V的配电网是不需要全线架设避雷线的,这对农网35 k V配网的线路防雷工作带来了非常大的困难。选择雷击事故较为严重的35 k V某线作为研究对...开展输电线路耐雷水平影响因素的研究是科学的输电线路防雷设计的基础。由于我国规程规定,35 k V的配电网是不需要全线架设避雷线的,这对农网35 k V配网的线路防雷工作带来了非常大的困难。选择雷击事故较为严重的35 k V某线作为研究对象,结合该线路的具体参数,利用电力系统电磁暂态计算程序(ATP-EMTP)进行仿真计算。利用所建立的仿真模型,针对接地电阻、绝缘子片数、有无避雷线、杆塔呼称高度、线路档距等因素进行了仿真,分析了其对35 k V输电线路耐雷水平的影响。同时,分析研究了加装线路型避雷器以及避雷器多种不同布置方式下,对输电线路绕击和反击线路耐雷水平的影响,为工程实际中35 k V线路的综合性防雷提供理论依据。展开更多
基金Project supported by Key Project of National Natural Science Foundation of China (50737003).
文摘In order to obtain reasonable schemes of arrester in converter stations, the arrester scheme of "Xiluodu-Guangdong HVDC ± 500 kV double circuit transmission" project against lighting induced overvoltage, which was designed according to the main principle of lightning protection in converter station, is discussed. A calculation of the lighting induced overvoltage in Zhaotong converter station un- der various operation modes is performed with ATP-EMTP software, then the surge arrester configuration of the converter station is decided, and the arrester protection schemes of smoothing reactor and neutral line are studied. It is concluded that additional protection is necessary because of the relatively large gap between protected disconnecting switch and arrester of metallic return transfer bus. Plus, the smoothing reactor (SR) arrester near the valve hall could be removed to improve the scheme’s economic performance.
文摘开展输电线路耐雷水平影响因素的研究是科学的输电线路防雷设计的基础。由于我国规程规定,35 k V的配电网是不需要全线架设避雷线的,这对农网35 k V配网的线路防雷工作带来了非常大的困难。选择雷击事故较为严重的35 k V某线作为研究对象,结合该线路的具体参数,利用电力系统电磁暂态计算程序(ATP-EMTP)进行仿真计算。利用所建立的仿真模型,针对接地电阻、绝缘子片数、有无避雷线、杆塔呼称高度、线路档距等因素进行了仿真,分析了其对35 k V输电线路耐雷水平的影响。同时,分析研究了加装线路型避雷器以及避雷器多种不同布置方式下,对输电线路绕击和反击线路耐雷水平的影响,为工程实际中35 k V线路的综合性防雷提供理论依据。