In this paper,the electrical fields along the insulator surface under different scenarios,such as asymmetric pollution on top/bottom surface,and uneven circumferential distribution of surface pollution,have been calcu...In this paper,the electrical fields along the insulator surface under different scenarios,such as asymmetric pollution on top/bottom surface,and uneven circumferential distribution of surface pollution,have been calculated with finite element method for field simulation.Tests on artificial pollution insulators are conducted to study the 50% withstand voltage U50 of artificial pollution suspension insulators under different NSDD(non-soluble deposit density)and asymmetric pollution on the top/bottom surface,and study the change of leakage current with air humidity under different voltage and different ESDD(equivalent salt deposit density).The result shows that asymmetric top/bottom surface pollution has a greater impact on the insulator electrical field distribution,and the leakage current will jump under low air humidity,if had large ESDD,which has practical meanings to the anti-pollution design of the transmission line under different pollution levels across the country.展开更多
基金Project Supported by Key Technology Research Programof SGCC(SGSC[2005]115)
文摘In this paper,the electrical fields along the insulator surface under different scenarios,such as asymmetric pollution on top/bottom surface,and uneven circumferential distribution of surface pollution,have been calculated with finite element method for field simulation.Tests on artificial pollution insulators are conducted to study the 50% withstand voltage U50 of artificial pollution suspension insulators under different NSDD(non-soluble deposit density)and asymmetric pollution on the top/bottom surface,and study the change of leakage current with air humidity under different voltage and different ESDD(equivalent salt deposit density).The result shows that asymmetric top/bottom surface pollution has a greater impact on the insulator electrical field distribution,and the leakage current will jump under low air humidity,if had large ESDD,which has practical meanings to the anti-pollution design of the transmission line under different pollution levels across the country.