期刊文献+

三相参数不对称的环状复杂配电网故障计算的新方法 被引量:6

A NEW APPROACH FOR FAULT CALCULATION IN ASYMMETRICAL THREE-PHASE AND WEAKLY MESHED DISTRIBUTION NETWORK
下载PDF
导出
摘要 根据少环配电网的结构特点,提出一种三相参数不对称的环状配电网故障计算新方法:将配电网分成不含环状结构的辐射状网络和不含辐射状结构的纯环状网络,从而通过回路阻抗矩阵来反映环网的影响,并利用叠加原理来进行整个配电网故障计算。该方法的主要特点在于: 采用abc三相模型,克服了由于配电网三相参数不对称所造成的对称分量法无法应用的缺点;无需形成复杂的三相参数不对称的含环网的配电网三相节点复数导纳或阻抗参数矩阵;能够自动适应网络拓扑结构的变化;可方便地计及限流器的作用;计算速度快,效率高,方法简单。算例表明文中方法是三相参数不对称的含环形网络配电网故障计算的一种十分简单且有效的方法。 According to the structure feature of the weakly meshed distribution network, a new method for fault calculation is proposed in this paper. The weakly meshed network is divided into two networks: one is the pure radial network and the other is the pure meshed network. The final solution is obtained by using the superposition principle. The proposed algorithm has many advantages: ① it is easy to deal with the unbalance in three phase by adopting phase component; ② the network nodal complex admittance matrices are avoided in fault calculation; ③ the method is adaptable to network topology changes; ④it is very simple o deal with the influence of fault current limiters; ⑤The approach is precise and effective. The numerical example shows that this method is very effective for fault calculation in asymmetrical three-phase and meshed distribution network.
作者 傅旭 王锡凡
出处 《中国电机工程学报》 EI CSCD 北大核心 2004年第11期64-68,共5页 Proceedings of the CSEE
关键词 配电网 故障计算 三相 对称分量法 阻抗参数 环网 限流器 阻抗矩阵 环状 环形网络 Power system Weakly meshed distribution system Fault calculation The decomposition of network Fault current limiters
  • 相关文献

参考文献14

二级参考文献44

共引文献265

同被引文献52

引证文献6

二级引证文献31

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部