针对间接蒸发冷却空调机组在数据中心应用时的补冷方式、补冷比例、压缩机补冷失效时的机房温升进行分析,同时对冷冻水补冷与压缩机补冷2种间接蒸发冷却空调机组在数据中心应用时的CLF和WUE以及2种补冷方式的应用场景进行分析。为间接蒸发冷却空调机组在数据中心补冷方式的选择提供了依据。
For the application of indirect evaporative cooling air conditioning unit in data center,it analyzes the supplemental cooling mode,proportion of supplemental cooling,and the room temperature rise when the compressor supplemental cooling is failed. At the same time,the CLF,WUE and the application scenarios of the two indirect evaporative cooling air conditioning units of cold water supplemental cooling and compressor supplemental cooling in the data center are analyzed. It provides a basis for the selection of supplementary cooling method when the indirect evaporative cooling unit is applied in the data center.